High Efficiency R22 Heat Recovery Unit Air Conditioning Chiller For Hotels / Hospitals

Categories Heat Recovery Unit
Brand Name: EuroKlimat
Model Number: EKAC
Certification: ISO9001, ISO14001, OHSAS18001, CRAA, CQC
Place of Origin: China
MOQ: 1 pcs
Price: Negotiation
Payment Terms: T/T or L/C
Supply Ability: 15,000pcs per month
Delivery Time: 10 working days after received your payment
Packaging Details: Carton
Product Name: Total Heat Recovery Modular Air-cooled Chiller
Nominal water supply capacity(m3/h): 16.3
Cooling Capacity(kW): 65.5
Heating Capacity(kW): 69
COP: 8.52
Max outgoing water temp.( °C): 55
Refrigerant: R22
Circuit water pump: Optional
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
  • Submit Buying Request
    • Product Details
    • Company Profile

    High Efficiency R22 Heat Recovery Unit Air Conditioning Chiller For Hotels / Hospitals

    12.1 High Efficiency Total Heat Recovery Modular Air-cooled Chiller


    Specifications:


    Model EKAC 230BRSREKAC 460BRSREKAC 690BRSREKAC 920BRSREKAC 1150BRSR

    EKAC

    1380BRSR

    Unit combinationMaster unitEKAC230BRSRMEKAC230BRSRMEKAC230BRSRMEKAC230BRSRMEKAC230BRSRM

    EKAC

    230BRSRM

    slave unit--EKAC230BRSRS2EKAC230BRSRS3EKAC230BRSRS4EKAC230BRSRS

    5EKAC

    230BRSRS

    Air conditioning modeNominal cooling capacitykW65.5131.0196.5262.0327.5393.0
    Nominal heating capacitykW69138207276345414
    Nominal cooling input powerkW19.438.858.277.697.0116.4
    Nominal heating input powerkW19.238.557.776.996.2115.4
    Water flow rate for nominal
    cooling capacity
    3
    m /h
    11.322.533.845.156.367.6
    Water flow rate for nominal
    heating capacity
    3
    m /h
    11.923.735.647.559.371.2
    Hot water modeNominal water supply capacitym3/h16.332.749.065.481.798.0
    Nominal heating capacitykW76152228304380456
    Total power of nominal heating capacitykW18.436.755.173.591.8110.2
    Cooling + Heat recovery modeNominal cooling capacitykW59.7119.4179.1238.8298.5358.2
    Nominal heat recovery capacitykW76152228304380456
    Nominal input powerkW16.332.648.965.281.597.8
    Nominal water supply capacity at heat recovery side3m /h16.332.648.965.281.597.8
    Nominal water flow at
    evaporator side
    3
    m /h
    10.320.530.841.151.361.6
    Power supply 380V/3N~/50Hz
    Flow control Electronic expansion valve
    Refrigerant R22
    Heat exchanger
    type
    Air conditioning side braze-welded panel-type heat exchanger
    Hot water side High-efficiency bucket heat exchanger
    CompressorType Fully hermetic volute compressor
    Lubricant Mineral oil (SUNISO 3GS)
    Qty.Set24681012
    FanType High-efficiency low-noise axial fan
    Qty.Set24681012
    Water resistanceAir conditioning sidekPa454545454545
    Hot water sidekPa757575757575
    Minimum diameter for water pipesAir conditioning sideinch≥2≥3≥3≥4≥4≥5
    Hot water sideinch≥2≥3≥4≥4≥5≥5
    DimensionsL x Hmm2012×1840
    Width 88021253370461558607105
    Power cable specificationSection area of live linemm2≥10≥35≥70≥95≥120≥150
    Qty. of live lines 3
    Section area of null linemm2≥4
    Qty. of null lines 1
    Section area of grounding linemm2≥10≥16≥35≥50≥60≥75
    Qty. of grounding lines 1
    Unit weightNet weightkg60012001800240030003600
    Operating weightkg62012401860248031003720

    Note:
    ■ Air conditioning mode: Test conditions for nominal cooling capacity: outlet water temperature 7°C; water flow: 0.172 m3/(h·kW); outdoor ambient temperature
    35°C. Test conditions for nominal heating capacity: outlet water temperature: 45°C; water flow: 0.172 m3/(h·kW); temperature of outdoor dry/wet bulb: 7°C/6°C.
    ■ Cooling + Heat recovery mode Test conditions for nominal cooling capacity: Hot water side: temperature of outlet water 45°C, water flow 0.215 m3/(h·kW); Air
    conditioning side: temperature of outlet water 7°C, water flow 0.172 m3/(h·kW);
    ■ Hot water mode: Test conditions for nominal water flow: Ambient temp: 20/15°C; outlet water temp: 45°C; water flow of cooling + heat recovery mode.
    ■ Water resistance at the air conditioner side includes water pressure drop of the unit and the attached Y-shaped filter.
    ■ Water resistance at the hot water side includes water pressure drop of the unit and does not include the pressure drop at the Y-shaped filter and other
    components.
    ■ Pipes outside the unit need to be customized and installed on site. The diameter of the pipes must meet design requirements. EK does not provide the pipes.
    ■ Full heat recovery units and other units can be combined to form partial heat recovery modular system. Full heat recovery units can also be combined to form a
    total heat recovery system. Modular units can be formed using the 1~16 basic modules. The above table lists the parameters for common module combinations.
    ■ For on-site electric wiring, see the name plate or installation menu of the unit.


    Description:


    Total heat recovery Air-cooled chiller/heat pump model feature a brand new European design and R&D technology.They are a perfect combination of air-cooled chilled/hot water unit and air source heat pump hot water unit.

    Besides providing cooling in summer and heating in winter for buildings, units of this series can also provide around-the-clock hot water of 40°C -55°C no matter in what climate. Therefore, they can completely replace boilers and save customers a sum of investment. This is not only cost effective but also environment friendly. In addition, absorbing heat discharged by air conditioners can also avoid"urban heat island effect".


    Providing Free Hot Water and Saving Investment


    In addition to air conditioning, the modular total heat recovery air-cooled chiller/heat pump also works as a boiler to recycle waste heat and provide hot water at 40°C - 55°C free of charge. This saves investment and installation space for a boiler.

    Industry-Leading Hybrid Connection Technology

    As an industry pioneer, EK launched units that support hybrid modular connection with common air cooled heat pump units. Total heat recovery units can be networked with standard modular units to form a partial heat recovery modular system, and can also be networked with total heat recovery units to form a Total heat recovery system to meet different heat recovery requirements.


    Efficient and Environment Friendly,Saving More Than 60% of Energy


    The unit recycles waste heat generated during condensation to improve the COP up to 8.32, saving more than 60% of energy compared with common modular units.Recycling heat is also environment friendly, and helps to avoid the "Heat Island Effect".


    Comfortable and Cost Effective


    By running a total heat recovery modular unit in the cooling + hot water mode, a customer can enjoy comfortable air conditioning as well as free hot water, especially during transitional seasons. This makes the unit energy saving and environment friendly.


    Applications:

    Units of this series are widely used in places where hot water is required, such as hotels, hospitals, schools, villas and bathing centers.


    Competitive Advantage:


    Five running modes for choosing


    Cooling Mode

    When cooling is required but hot water is not required, a customer can choose the cooling mode.In this case, the unit works in cooling only mode, the same as a common air-cooled heat pump unit.

    Heating mode

    When heating is required but hot water is not required, a customer can choose the heating mode.In this case, the unit works in heating only mode,the same as a common air-cooled heat pump unit.

    Cooling + Hot Water

    When both cooling and hot water are required, a customer can choose the cooling + hot water mode.In this case, the unit automatically starts the air conditioning module to provide chilled water for the air conditioner, and starts the hot water module to generate hot water.

    Heating + Hot Water

    When both heating and hot water are required, a customer can choose the heating + hot water mode.In this case, the unit takes air conditioning as the first priority, and generates hot water in idle periods to meet hot water requirement. A customer can also specified a time period when the unit works in hot water mode.

    Hot Water Mode

    When hot water is required and air conditioning is not required, a customer can choose the hot water mode. In this case, the unit only provides hot water, and works as a common air source heat pump hot water unit.